Wire Sizing

What Size Wire for 30 Amp 200 Feet Away

Table-based wire size estimate for 30 amps at 200 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
6 AWG
Voltage drop: 2.25% (5.403V)
Voltage at load: 234.60V
Ampacity used: 55 A (60°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
4 AWG
Voltage drop: 2.33% (5.581V)
Voltage at load: 234.42V
Ampacity used: 55 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 200 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
10 AWG30A12.638V5.27%227.36V
8 AWG40A8.367V3.49%231.63V
6 AWGREC55A5.403V2.25%234.6V
4 AWG70A3.541V1.48%236.46V
3 AWG85A2.923V1.22%237.08V

Table shows nearby candidate sizes for 30A at 200 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Pool motor or variable-speed drive

This generic estimate also applies to a pool pump. A drive-equipped pump may have input-current and protective-device instructions that differ from a directly connected motor. Confirm the equipment data, bonding and ground-fault protection before using the conductor result as part of a pool installation design.

Why this copper conductor?

6 AWG has a site ampacity of 55 A against a required 30 A. Table 9 lists R = 0.49 and XL = 0.064 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.4502 Ω/kft. Substituting the actual load into 2 × 30 × 200 × 0.4502 / 1000 gives 5.403 V (2.25%).

The next smaller size, 8 AWG, has 40 A of site ampacity and 3.49% drop on this route. It fails the voltage-drop target.

3% route-length limit: 266.5 ft one way; remaining margin: 66.5 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 30 A · 200 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target30 A / 200 ft / 240 V30 A6 AWG5.403 V (2.25%) / 234.597 V
Reserve more voltage: 2% target30 A / 200 ft / 240 V30 A4 AWG3.541 V (1.48%) / 236.459 V
Pool pump: Hypothetical motor conductor requirement = 1.25 × A30 A / 200 ft / 240 V37.5 A6 AWG5.403 V (2.25%) / 234.597 V

The alternative ampacity requirement is a sensitivity check only. It leaves voltage drop at running current and does not model a motor starting surge. Determine the applicable full-load-current basis and duty allowance separately from this hypothetical factor.

3% → 2% changes 6 AWG → 4 AWG. Load-voltage gain: 1.861 V. Original conductor’s 2% length limit: 177.7 ft one way.

Also covers: pool pump 30 amp 200 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • Read the motor or drive instructions for current, voltage and connection limits. A variable-speed pump may have different input characteristics from a directly connected induction motor.
  • Determine motor conductor ampacity using the applicable Article 430 current basis and duty allowance, then check Article 680 requirements. The generic running-current estimate does not perform either code calculation.
  • Ground-fault protection and equipotential bonding address hazards that are independent of voltage drop. Confirm the pump, nearby metal parts and supply arrangement meet the applicable pool rules.
  • Include the complete panel-to-pump route and test the starting or drive operating-voltage range. Outdoor raceways and connections must be suitable for moisture and the installed environment.

Key Considerations

The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.

For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.

Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.

Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 30 amp circuit at 200 feet?▾
For a 30A/240V circuit at 200 feet, use 6 AWG copper (2.25% drop) or 4 AWG aluminum. The ampacity check uses 30A; voltage drop uses the actual 30A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 30 amp circuit?▾
At 30A over 200 ft, use 4 AWG aluminum (2.33% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator