What Size Wire for 30 Amp 100 Feet Away
Table-based wire size estimate for 30 amps at 100 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 100 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 14 AWG | 15A | 16.041V | 6.68% | 223.96V | |
| 12 AWG | 20A | 10.415V | 4.34% | 229.59V | |
| 10 AWGREC | 30A | 6.319V | 2.63% | 233.68V | |
| 8 AWG | 40A | 4.183V | 1.74% | 235.82V | |
| 6 AWG | 55A | 2.701V | 1.13% | 237.3V |
Table shows nearby candidate sizes for 30A at 100 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Small HVAC circuit protection
For HVAC equipment, check the nameplate before using this generic estimate. Compressor protection may follow equipment-specific rules that differ from general receptacle-circuit practice. The engine deliberately retains conservative small-conductor limits; it does not infer an Article 440 exception from the HVAC label or the installed breaker.
Operating boundaries: 30 A, 100 ft, 240 V, copper
Ampacity sets the minimum: 10 AWG supports 30 A (60°C column) against the 30.000 A requirement. At 30 A it can reach 113.940 ft before the 3% drop target takes over. Shortening this 100 ft route alone cannot reduce the ampacity floor. One set suffices in this model.
12 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 20.000 A. At the present 100 ft, its drop ceiling is 20.739 A. Both checks first allow that smaller conductor at or below 20.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.
For the selected 10 AWG, increasing load beyond 30.000 A changes the choice: ampacity reaches its limit first. That leaves 0.000 A above the present load. With current fixed, route growth above 113.940 ft also requires reselection, a margin of 13.940 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 30 A, the existing conductor’s length ceiling falls to 75.960 ft; at 100 ft, its combined current ceiling becomes 22.788 A. The unchanged inputs now select 8 AWG, giving 4.183 V (1.743%).
- Current −10%: 27.000 A / 100.000 ft → 10 AWG (2.370%).
- Current +10%: 33.000 A / 100.000 ft → 8 AWG (1.917%).
- Route −10%: 30.000 A / 90.000 ft → 10 AWG (2.370%).
- Route +10%: 30.000 A / 110.000 ft → 10 AWG (2.896%).
Basis: Z = 1.0532 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 30 A · 100 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 30 A / 100 ft / 240 V | 30 A | 10 AWG | 6.319 V (2.63%) / 233.681 V |
| Reserve more voltage: 2% target | 30 A / 100 ft / 240 V | 30 A | 8 AWG | 4.183 V (1.74%) / 235.817 V |
| HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A | 30 A / 100 ft / 240 V | 37.5 A | 8 AWG | 4.183 V (1.74%) / 235.817 V |
Also covers: hvac 30 amp 100 feet
The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.
- Use nameplate MCA for conductors and MOCP for protection; neither is running current. Do not multiply an already marked MCA again. Check starting voltage, roof temperature, grouping, disconnect terminals and equipment protection rules separately.
Key Considerations
Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 30 amp circuit at 100 feet?▾
Can I use aluminum wire for a 30 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator