Wire Sizing

What Size Wire for 30 Amp 50 Feet Away

Pre-calculated NEC-compliant wire size for 30 amps at 50 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
10 AWG
Voltage drop: 1.55% (3.72V)
Voltage at load: 236.3V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
8 AWG
Voltage drop: 1.6% (3.84V)
Voltage at load: 236.2V
Controlling factor: Ampacity (NEC 310.16)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 50 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A9.42V3.93%230.6V
12 AWG20A5.94V2.48%234.1V
10 AWGREC30A3.72V1.55%236.3V
8 AWG50A2.33V0.97%237.7V
6 AWG65A1.47V0.61%238.5V
4 AWG85A0.92V0.39%239.1V
3 AWG100A0.74V0.31%239.3V
2 AWG115A0.58V0.24%239.4V
1 AWG130A0.46V0.19%239.5V
1/0 AWG150A0.37V0.15%239.6V
2/0 AWG175A0.29V0.12%239.7V
3/0 AWG200A0.23V0.1%239.8V
4/0 AWG230A0.18V0.08%239.8V
250 kcmil255A0.15V0.06%239.8V
300 kcmil285A0.13V0.05%239.9V
350 kcmil310A0.11V0.05%239.9V
400 kcmil335A0.1V0.04%239.9V
500 kcmil380A0.08V0.03%239.9V

Table shows all standard AWG/kcmil sizes for 30A at 50 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 30A circuit at 50 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 30 amp service at 50 feet?
For a 30A/240V circuit at 50 feet, use 10 AWG copper (1.55% drop) or 8 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 30 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 30A at 50 feet, use 8 AWG aluminum (1.6% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 30A circuit at 50 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator