What Size Wire for 30 Amp 50 Feet Away
Table-based wire size estimate for 30 amps at 50 feet on a 240V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 50 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 14 AWG | 15A | 8.02V | 3.34% | 231.98V | |
| 12 AWG | 20A | 5.207V | 2.17% | 234.79V | |
| 10 AWGREC | 30A | 3.16V | 1.32% | 236.84V | |
| 8 AWG | 40A | 2.092V | 0.87% | 237.91V | |
| 6 AWG | 55A | 1.351V | 0.56% | 238.65V |
Table shows nearby candidate sizes for 30A at 50 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Appliance supply configuration
Read the appliance connection diagram to establish whether the supply needs a neutral as well as an equipment grounding conductor. The displayed single-phase loss concerns the loaded conductor pair only. It does not size a neutral for internal line-to-neutral loads or determine which cable assembly is permitted for the appliance.
Why this copper conductor?
10 AWG has a site ampacity of 30 A against a required 30 A. Table 9 lists R = 1.2 and XL = 0.063 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 1.0532 Ω/kft. Substituting the actual load into 2 × 30 × 50 × 1.0532 / 1000 gives 3.160 V (1.32%).
The next smaller size, 12 AWG, has 20 A of site ampacity and 2.17% drop on this route. It fails the ampacity requirement.
3% route-length limit: 113.9 ft one way; remaining margin: 63.9 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 30 A · 50 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 30 A / 50 ft / 240 V | 30 A | 10 AWG | 3.160 V (1.32%) / 236.840 V |
| Reserve more voltage: 2% target | 30 A / 50 ft / 240 V | 30 A | 10 AWG | 3.160 V (1.32%) / 236.840 V |
| General branch circuit: Same assumed watts at twice the supply voltage | 15 A / 50 ft / 480 V | 15 A | 14 AWG | 4.010 V (0.84%) / 475.990 V |
The higher-voltage row keeps assumed electrical power constant by halving current. It is useful only for equipment listed for that alternative supply; it does not authorize reconnecting a fixed-voltage appliance. The percent drop changes with both current and supply voltage.
3% → 2% retains 10 AWG → 10 AWG. Load-voltage gain: 0.000 V. Original conductor’s 2% length limit: 76.0 ft one way.
Key Considerations
The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 30 amp circuit at 50 feet?▾
Can I use aluminum wire for a 30 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator