Wire Size for HVAC Unit — 30 Amp 75 Feet
Pre-calculated NEC-compliant wire size for 30 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.
Recommended Wire Size
Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 14 AWG | 15A | 14.13V | 5.89% | 225.9V | |
| 12 AWG | 20A | 8.91V | 3.71% | 231.1V | |
| 10 AWGREC | 30A | 5.58V | 2.33% | 234.4V | |
| 8 AWG | 50A | 3.5V | 1.46% | 236.5V | |
| 6 AWG | 65A | 2.21V | 0.92% | 237.8V | |
| 4 AWG | 85A | 1.39V | 0.58% | 238.6V | |
| 3 AWG | 100A | 1.1V | 0.46% | 238.9V | |
| 2 AWG | 115A | 0.87V | 0.36% | 239.1V | |
| 1 AWG | 130A | 0.69V | 0.29% | 239.3V | |
| 1/0 AWG | 150A | 0.55V | 0.23% | 239.5V | |
| 2/0 AWG | 175A | 0.44V | 0.18% | 239.6V | |
| 3/0 AWG | 200A | 0.34V | 0.14% | 239.7V | |
| 4/0 AWG | 230A | 0.27V | 0.11% | 239.7V | |
| 250 kcmil | 255A | 0.23V | 0.1% | 239.8V | |
| 300 kcmil | 285A | 0.19V | 0.08% | 239.8V | |
| 350 kcmil | 310A | 0.17V | 0.07% | 239.8V | |
| 400 kcmil | 335A | 0.14V | 0.06% | 239.9V | |
| 500 kcmil | 380A | 0.12V | 0.05% | 239.9V |
Table shows all standard AWG/kcmil sizes for 30A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.
Key Considerations
For a 30A circuit at 75 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.
Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.
Frequently Asked Questions
What size wire do I need for a 30 amp service at 75 feet?▾
Can I use aluminum wire for a 30 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator