What Size Wire for 30 Amp 75 Feet Away
Table-based wire size estimate for 30 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.
Updated October 24, 2026
Recommended Wire Size
Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 14 AWG | 15A | 14.13V | 5.89% | 225.9V | |
| 12 AWG | 20A | 8.91V | 3.71% | 231.1V | |
| 10 AWGREC | 30A | 5.58V | 2.33% | 234.4V | |
| 8 AWG | 50A | 3.5V | 1.46% | 236.5V | |
| 6 AWG | 65A | 2.21V | 0.92% | 237.8V |
Table shows nearby candidate sizes for 30A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
HVAC equipment-specific instructions
The former HVAC scenario is included. Verify the actual MCA and the permitted protective-device type shown by the manufacturer. A fuse-only instruction is not interchangeable with a breaker selection, and a generic running-current calculation cannot establish the required overcurrent arrangement even if the wire recommendation meets the drop target.
Operating boundaries: 30 A, 75 ft, 240 V, copper
Ampacity sets the minimum: 10 AWG supports 30 A against the 30.000 A requirement. At 30 A it can reach 96.774 ft before the 3% drop target takes over. Shortening this 75 ft route alone cannot reduce the ampacity floor. One set suffices in this model.
12 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 20.000 A. At the present 75 ft, its drop ceiling is 24.242 A. Both checks first allow that smaller conductor at or below 20.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.
For the selected 10 AWG, increasing load beyond 30.000 A changes the choice: ampacity reaches its limit first. That leaves 0.000 A above the present load. With current fixed, route growth above 96.774 ft also requires reselection, a margin of 21.774 ft.
A 2% budget is 4.800 V instead of 7.200 V. At 30 A, the existing conductor’s length ceiling falls to 64.516 ft; at 75 ft, its combined current ceiling becomes 25.806 A. The unchanged inputs now select 8 AWG, giving 3.501 V (1.459%).
- Current −10%: 27.000 A / 75.000 ft → 10 AWG (2.092%).
- Current +10%: 33.000 A / 75.000 ft → 8 AWG (1.605%).
- Route −10%: 30.000 A / 67.500 ft → 10 AWG (2.093%).
- Route +10%: 30.000 A / 82.500 ft → 10 AWG (2.558%).
Basis: R = 1.24 Ω/kft at 75°C; Imax = min(ampacity / 1, V × target × 1000 / (2 × L × R)); Lmax = V × target × 1000 / (2 × I × R). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.
Which assumption changes this selection?
copper: 30 A · 75 ft · 240 V. Alternatives are hypothetical; all results use the site resistance table.
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 30 A / 75 ft / 240 V | 30 A | 10 AWG | 5.580 V (2.33%) / 234.420 V |
| Reserve more voltage: 2% target | 30 A / 75 ft / 240 V | 30 A | 8 AWG | 3.501 V (1.46%) / 236.499 V |
| HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A | 30 A / 75 ft / 240 V | 37.5 A | 8 AWG | 3.501 V (1.46%) / 236.499 V |
Also covers: hvac 30 amp 75 feet
This merged scenario shares the route inputs above. Apply the Key Considerations below; any additional equipment conditions are listed here.
- Use nameplate MCA for conductors and MOCP for protection; neither is running current. Do not multiply an already marked MCA again. Check starting voltage, roof temperature, grouping, disconnect terminals and equipment protection rules separately.
Key Considerations
Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 30 amp circuit at 75 feet?▾
Can I use aluminum wire for a 30 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator