Wire Sizing

What Size Wire for 30 Amp 75 Feet Away

Table-based wire size estimate for 30 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
10 AWG
Voltage drop: 1.97% (4.739V)
Voltage at load: 235.26V
Ampacity used: 30 A (60°C column). Controlling factor: Ampacity (NEC 310.16)
Aluminum
8 AWG
Voltage drop: 2.14% (5.127V)
Voltage at load: 234.87V
Ampacity used: 35 A (60°C column). Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A12.031V5.01%227.97V
12 AWG20A7.811V3.25%232.19V
10 AWGREC30A4.739V1.97%235.26V
8 AWG40A3.138V1.31%236.86V
6 AWG55A2.026V0.84%237.97V

Table shows nearby candidate sizes for 30A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

HVAC equipment-specific instructions

This estimate also applies to HVAC equipment. Verify the actual MCA and the permitted protective-device type shown by the manufacturer. A fuse-only instruction is not interchangeable with a breaker selection, and a generic running-current calculation cannot establish the required overcurrent arrangement even if the wire recommendation meets the drop target.

Operating boundaries: 30 A, 75 ft, 240 V, copper

Ampacity sets the minimum: 10 AWG supports 30 A (60°C column) against the 30.000 A requirement. At 30 A it can reach 113.940 ft before the 3% drop target takes over. Shortening this 75 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

12 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 20.000 A. At the present 75 ft, its drop ceiling is 27.653 A. Both checks first allow that smaller conductor at or below 20.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.

For the selected 10 AWG, increasing load beyond 30.000 A changes the choice: ampacity reaches its limit first. That leaves 0.000 A above the present load. With current fixed, route growth above 113.940 ft also requires reselection, a margin of 38.940 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 30 A, the existing conductor’s length ceiling falls to 75.960 ft; at 75 ft, its combined current ceiling becomes 30.000 A. The unchanged inputs still select 10 AWG, giving 4.739 V (1.975%).

  • Current −10%: 27.000 A / 75.000 ft → 10 AWG (1.777%).
  • Current +10%: 33.000 A / 75.000 ft → 8 AWG (1.438%).
  • Route −10%: 30.000 A / 67.500 ft → 10 AWG (1.777%).
  • Route +10%: 30.000 A / 82.500 ft → 10 AWG (2.172%).

Basis: Z = 1.0532 Ω/kft (effective impedance, Table 9, steel conduit, PF 0.85; NEC 2017 Table 9 values); Imax = min(ampacity / 1, V × target × 1000 / (2 × L × Z)); Lmax = V × target × 1000 / (2 × I × Z). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 30 A · 75 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target30 A / 75 ft / 240 V30 A10 AWG4.739 V (1.97%) / 235.261 V
Reserve more voltage: 2% target30 A / 75 ft / 240 V30 A10 AWG4.739 V (1.97%) / 235.261 V
HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A30 A / 75 ft / 240 V37.5 A8 AWG3.138 V (1.31%) / 236.862 V

Also covers: hvac 30 amp 75 feet

The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.

  • Use nameplate MCA for conductors and MOCP for protection; neither is running current. Do not multiply an already marked MCA again. Check starting voltage, roof temperature, grouping, disconnect terminals and equipment protection rules separately.

Key Considerations

Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 30 amp circuit at 75 feet?▾
For a 30A/240V circuit at 75 feet, use 10 AWG copper (1.97% drop) or 8 AWG aluminum. The ampacity check uses 30A; voltage drop uses the actual 30A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 30 amp circuit?▾
At 30A over 75 ft, use 8 AWG aluminum (2.14% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator