Wire Sizing

What Size Wire for 30 Amp 75 Feet Away

Table-based wire size estimate for 30 amps at 75 feet on a 240V single-phase circuit. Immediate answer below.

Updated October 24, 2026

Recommended Wire Size

Copper
10 AWG
Voltage drop: 2.33% (5.580V)
Voltage at load: 234.42V
Controlling factor: Ampacity (NEC 310.16)
Aluminum
8 AWG
Voltage drop: 2.40% (5.760V)
Voltage at load: 234.24V
Controlling factor: Ampacity (NEC 310.16)

Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 75 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A14.13V5.89%225.9V
12 AWG20A8.91V3.71%231.1V
10 AWGREC30A5.58V2.33%234.4V
8 AWG50A3.5V1.46%236.5V
6 AWG65A2.21V0.92%237.8V

Table shows nearby candidate sizes for 30A at 75 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

HVAC equipment-specific instructions

The former HVAC scenario is included. Verify the actual MCA and the permitted protective-device type shown by the manufacturer. A fuse-only instruction is not interchangeable with a breaker selection, and a generic running-current calculation cannot establish the required overcurrent arrangement even if the wire recommendation meets the drop target.

Operating boundaries: 30 A, 75 ft, 240 V, copper

Ampacity sets the minimum: 10 AWG supports 30 A against the 30.000 A requirement. At 30 A it can reach 96.774 ft before the 3% drop target takes over. Shortening this 75 ft route alone cannot reduce the ampacity floor. One set suffices in this model.

12 AWG cannot carry this assumed load: its current ceiling after the ×1 allowance is 20.000 A. At the present 75 ft, its drop ceiling is 24.242 A. Both checks first allow that smaller conductor at or below 20.000 A, a reduction of 10.000 A. Distance alone cannot fix its ampacity shortfall.

For the selected 10 AWG, increasing load beyond 30.000 A changes the choice: ampacity reaches its limit first. That leaves 0.000 A above the present load. With current fixed, route growth above 96.774 ft also requires reselection, a margin of 21.774 ft.

A 2% budget is 4.800 V instead of 7.200 V. At 30 A, the existing conductor’s length ceiling falls to 64.516 ft; at 75 ft, its combined current ceiling becomes 25.806 A. The unchanged inputs now select 8 AWG, giving 3.501 V (1.459%).

  • Current −10%: 27.000 A / 75.000 ft → 10 AWG (2.092%).
  • Current +10%: 33.000 A / 75.000 ft → 8 AWG (1.605%).
  • Route −10%: 30.000 A / 67.500 ft → 10 AWG (2.093%).
  • Route +10%: 30.000 A / 82.500 ft → 10 AWG (2.558%).

Basis: R = 1.24 Ω/kft at 75°C; Imax = min(ampacity / 1, V × target × 1000 / (2 × L × R)); Lmax = V × target × 1000 / (2 × I × R). Boundaries are displayed to three decimals; selection uses unrounded values. These are load changes, not permission to change a breaker.

Which assumption changes this selection?

copper: 30 A · 75 ft · 240 V. Alternatives are hypothetical; all results use the site resistance table.

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target30 A / 75 ft / 240 V30 A10 AWG5.580 V (2.33%) / 234.420 V
Reserve more voltage: 2% target30 A / 75 ft / 240 V30 A8 AWG3.501 V (1.46%) / 236.499 V
HVAC equipment: Hypothetical nameplate MCA = 1.25 × running A30 A / 75 ft / 240 V37.5 A8 AWG3.501 V (1.46%) / 236.499 V

Also covers: hvac 30 amp 75 feet

This merged scenario shares the route inputs above. Apply the Key Considerations below; any additional equipment conditions are listed here.

  • Use nameplate MCA for conductors and MOCP for protection; neither is running current. Do not multiply an already marked MCA again. Check starting voltage, roof temperature, grouping, disconnect terminals and equipment protection rules separately.

Key Considerations

Use actual load current; check continuous duty separately. The site retains small-conductor protection limits. Verify cable and terminal temperature, equipment voltage range, upstream loss and connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 30 amp circuit at 75 feet?▾
For a 30A/240V circuit at 75 feet, use 10 AWG copper (2.33% drop) or 8 AWG aluminum. The ampacity check uses 30A; voltage drop uses the actual 30A. Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 30 amp circuit?▾
At 30A over 75 ft, use 8 AWG aluminum (2.40% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator