Wire Sizing

Wire Size for HVAC Unit — 50 Amp 150 Feet

Pre-calculated NEC-compliant wire size for 50 amps at 150 feet on a 240V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
4 AWG
Voltage drop: 1.93% (4.62V)
Voltage at load: 235.4V
Controlling factor: Voltage Drop (3% limit)
Aluminum
3 AWG
Voltage drop: 2.52% (6.05V)
Voltage at load: 234V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 150 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A47.1V19.63%192.9V
12 AWG20A29.7V12.38%210.3V
10 AWG30A18.6V7.75%221.4V
8 AWG50A11.67V4.86%228.3V
6 AWG65A7.37V3.07%232.6V
4 AWGREC85A4.62V1.93%235.4V
3 AWG100A3.68V1.53%236.3V
2 AWG115A2.91V1.21%237.1V
1 AWG130A2.31V0.96%237.7V
1/0 AWG150A1.83V0.76%238.2V
2/0 AWG175A1.45V0.6%238.5V
3/0 AWG200A1.15V0.48%238.9V
4/0 AWG230A0.91V0.38%239.1V
250 kcmil255A0.77V0.32%239.2V
300 kcmil285A0.64V0.27%239.4V
350 kcmil310A0.55V0.23%239.4V
400 kcmil335A0.48V0.2%239.5V
500 kcmil380A0.39V0.16%239.6V

Table shows all standard AWG/kcmil sizes for 50A at 150 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 50A circuit at 150 feet on 240V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 50 amp service at 150 feet?
For a 50A/240V circuit at 150 feet, use 4 AWG copper (1.93% drop) or 3 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 50 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 50A at 150 feet, use 3 AWG aluminum (2.52% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 50A circuit at 150 feet on 240V, exceeding 3% means the load receives less than 232.8V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator