Wire Sizing

What Size Wire for 15 Amp 50 Feet Away

Pre-calculated NEC-compliant wire size for 15 amps at 50 feet on a 120V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
12 AWG
Voltage drop: 2.48% (2.97V)
Voltage at load: 117V
Controlling factor: Voltage Drop (3% limit)
Aluminum
10 AWG
Voltage drop: 2.55% (3.06V)
Voltage at load: 116.9V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 50 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A4.71V3.93%115.3V
12 AWGREC20A2.97V2.48%117V
10 AWG30A1.86V1.55%118.1V
8 AWG50A1.17V0.97%118.8V
6 AWG65A0.74V0.61%119.3V
4 AWG85A0.46V0.39%119.5V
3 AWG100A0.37V0.31%119.6V
2 AWG115A0.29V0.24%119.7V
1 AWG130A0.23V0.19%119.8V
1/0 AWG150A0.18V0.15%119.8V
2/0 AWG175A0.15V0.12%119.9V
3/0 AWG200A0.11V0.1%119.9V
4/0 AWG230A0.09V0.08%119.9V
250 kcmil255A0.08V0.06%119.9V
300 kcmil285A0.06V0.05%119.9V
350 kcmil310A0.06V0.05%119.9V
400 kcmil335A0.05V0.04%120V
500 kcmil380A0.04V0.03%120V

Table shows all standard AWG/kcmil sizes for 15A at 50 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 15A circuit at 50 feet on 120V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 15 amp service at 50 feet?
For a 15A/120V circuit at 50 feet, use 12 AWG copper (2.48% drop) or 10 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 15 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 15A at 50 feet, use 10 AWG aluminum (2.55% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 15A circuit at 50 feet on 120V, exceeding 3% means the load receives less than 116.4V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator