Wire Sizing

What Size Wire for 15 Amp 50 Feet Away

Table-based wire size estimate for 15 amps at 50 feet on a 120V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
12 AWG
Voltage drop: 2.17% (2.604V)
Voltage at load: 117.40V
Ampacity used: 20 A (60°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
10 AWG
Voltage drop: 2.17% (2.600V)
Voltage at load: 117.40V
Ampacity used: 25 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 15 A × 1 = 15 A. Drop uses 15 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 50 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A4.01V3.34%115.99V
12 AWGREC20A2.604V2.17%117.4V
10 AWG30A1.58V1.32%118.42V
8 AWG40A1.046V0.87%118.95V
6 AWG55A0.675V0.56%119.32V

Table shows nearby candidate sizes for 15A at 50 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Small-conductor protection remains relevant

A short cable path does not permit a larger protective device just because voltage loss is low. Verify the conductor material, wiring method and applicable small-conductor protection limit. If the load is continuous, use its adjusted ampacity requirement separately; this general-purpose example assumes the entered operating current without a continuous-load multiplier.

Why this copper conductor?

12 AWG has a site ampacity of 20 A against a required 15 A. Table 9 lists R = 2 and XL = 0.068 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 1.7358 Ω/kft. Substituting the actual load into 2 × 15 × 50 × 1.7358 / 1000 gives 2.604 V (2.17%).

The next smaller size, 14 AWG, has 15 A of site ampacity and 3.34% drop on this route. It fails the voltage-drop target.

3% route-length limit: 69.1 ft one way; remaining margin: 19.1 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 15 A · 50 ft · 120 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target15 A / 50 ft / 120 V15 A12 AWG2.604 V (2.17%) / 117.396 V
Reserve more voltage: 2% target15 A / 50 ft / 120 V15 A10 AWG1.580 V (1.32%) / 118.420 V
General branch circuit: Same assumed watts at twice the supply voltage7.5 A / 50 ft / 240 V7.5 A14 AWG2.005 V (0.84%) / 237.995 V

The higher-voltage row keeps assumed electrical power constant by halving current. It is useful only for equipment listed for that alternative supply; it does not authorize reconnecting a fixed-voltage appliance. The percent drop changes with both current and supply voltage.

3% → 2% changes 12 AWG → 10 AWG. Load-voltage gain: 1.024 V. Original conductor’s 2% length limit: 46.1 ft one way.

Key Considerations

The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.

For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.

Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.

Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 15 amp circuit at 50 feet?▾
For a 15A/120V circuit at 50 feet, use 12 AWG copper (2.17% drop) or 10 AWG aluminum. The ampacity check uses 15A; voltage drop uses the actual 15A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 15 amp circuit?▾
At 15A over 50 ft, use 10 AWG aluminum (2.17% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 116.4V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator