What Size Wire for 15 Amp 75 Feet Away
Table-based wire size estimate for 15 amps at 75 feet on a 120V single-phase circuit. Immediate answer below.
Updated October 23, 2026
Recommended Wire Size
Required ampacity: 15 A × 1 = 15 A. Drop uses 15 A. Based on NEC Table 310.16 (75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 75 ft.
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 14 AWG | 15A | 7.07V | 5.89% | 112.9V | |
| 12 AWG | 20A | 4.46V | 3.71% | 115.5V | |
| 10 AWGREC | 30A | 2.79V | 2.33% | 117.2V | |
| 8 AWG | 50A | 1.75V | 1.46% | 118.2V | |
| 6 AWG | 65A | 1.1V | 0.92% | 118.9V |
Table shows nearby candidate sizes for 15A at 75 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Pool equipment connection details
This page includes the former pool-pump route. Determine whether the pump is permanently connected or supplied through a permitted receptacle arrangement, and verify its grounding and bonding instructions. The conductor comparison is a running-load estimate, not a motor protection calculation or a check of electrical safety near the pool.
Why this copper conductor?
10 AWG has a site ampacity of 30 A against a required 15 A. Its resistance is 1.24 Ω/kft. Substituting the actual load into 2 × 15 × 75 × 1.24 / 1000 gives 2.790 V (2.33%).
The next smaller size, 12 AWG, has 20 A of site ampacity and 3.71% drop on this route. It fails the voltage-drop target.
3% route-length limit: 96.8 ft one way; remaining margin: 21.8 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 15 A · 75 ft · 120 V. Alternatives are hypothetical; all results use the site resistance table.
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 15 A / 75 ft / 120 V | 15 A | 10 AWG | 2.790 V (2.33%) / 117.210 V |
| Reserve more voltage: 2% target | 15 A / 75 ft / 120 V | 15 A | 8 AWG | 1.750 V (1.46%) / 118.249 V |
| Pool pump: Hypothetical motor conductor requirement = 1.25 × A | 15 A / 75 ft / 120 V | 18.75 A | 10 AWG | 2.790 V (2.33%) / 117.210 V |
The alternative ampacity requirement is a sensitivity check only. It leaves voltage drop at running current and does not model a motor starting surge. Determine the applicable full-load-current basis and duty allowance separately from this hypothetical factor.
3% → 2% changes 10 AWG → 8 AWG. Load-voltage gain: 1.040 V. Original conductor’s 2% length limit: 64.5 ft one way.
Also covers: pool pump 15 amp 75 feet
This merged scenario shares the route inputs above. Apply the Key Considerations below; any additional equipment conditions are listed here.
- Read the motor or drive instructions for current, voltage and connection limits. A variable-speed pump may have different input characteristics from a directly connected induction motor.
- Determine motor conductor ampacity using the applicable Article 430 current basis and duty allowance, then check Article 680 requirements. The generic running-current estimate does not perform either code calculation.
- Ground-fault protection and equipotential bonding address hazards that are independent of voltage drop. Confirm the pump, nearby metal parts and supply arrangement meet the applicable pool rules.
- Include the complete panel-to-pump route and test the starting or drive operating-voltage range. Outdoor raceways and connections must be suitable for moisture and the installed environment.
Key Considerations
The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 15 amp circuit at 75 feet?▾
Can I use aluminum wire for a 15 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator