What Size Wire for 15 Amp 100 Feet Away
Table-based wire size estimate for 15 amps at 100 feet on a 120V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 15 A × 1 = 15 A. Drop uses 15 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 100 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 14 AWG | 15A | 8.02V | 6.68% | 111.98V | |
| 12 AWG | 20A | 5.207V | 4.34% | 114.79V | |
| 10 AWGREC | 30A | 3.16V | 2.63% | 116.84V | |
| 8 AWG | 40A | 2.092V | 1.74% | 117.91V | |
| 6 AWG | 55A | 1.351V | 1.13% | 118.65V |
Table shows nearby candidate sizes for 15A at 100 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Well-pump cable assembly
For a well pump, this estimate assumes the entered distance covers the complete electrical path. Check whether the motor uses a control box and which conductors carry operating current. A pump cable diagram can differ from a simple two-wire appliance circuit; verify the manufacturer’s cable selection method before accepting this generic result.
Why this copper conductor?
10 AWG has a site ampacity of 30 A against a required 15 A. Table 9 lists R = 1.2 and XL = 0.063 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 1.0532 Ω/kft. Substituting the actual load into 2 × 15 × 100 × 1.0532 / 1000 gives 3.160 V (2.63%).
The next smaller size, 12 AWG, has 20 A of site ampacity and 4.34% drop on this route. It fails the voltage-drop target.
3% route-length limit: 113.9 ft one way; remaining margin: 13.9 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 15 A · 100 ft · 120 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 15 A / 100 ft / 120 V | 15 A | 10 AWG | 3.160 V (2.63%) / 116.840 V |
| Reserve more voltage: 2% target | 15 A / 100 ft / 120 V | 15 A | 8 AWG | 2.092 V (1.74%) / 117.908 V |
| Well pump: Hypothetical down-well cable adds 25% to route | 15 A / 125 ft / 120 V | 15 A | 8 AWG | 2.615 V (2.18%) / 117.385 V |
The additional route represents cable omitted below the wellhead. It changes impedance loss without changing running current. Replace the assumed extra length with the measured depth and actual route; starting behavior still needs its own check.
3% → 2% changes 10 AWG → 8 AWG. Load-voltage gain: 1.068 V. Original conductor’s 2% length limit: 76.0 ft one way.
Also covers: well pump 15 amp 100 feet
The same amps, distance and voltage above also describe this equipment, so the result applies to it too. Apply the Key Considerations below; extra equipment conditions are listed here.
- Include the cable down the well as well as the horizontal trench and the route from the panel to the wellhead. The entered distance is the complete one-way electrical path, not just the surface separation.
- The stated amperes are assumed running current. The estimate applies no motor allowance: separately determine code full-load current and the applicable conductor factor under Article 430. A continuous-duty single motor commonly requires 125% of code full-load current, which need not equal measured running current.
- A submersible motor must start against its hydraulic load. Check the pump maker’s cable-length limits and starting-voltage requirements; a steady-state calculation cannot model a pressure switch, control box or generator transient.
- Verify submersible cable, underwater splice and terminal suitability. Pump overload protection and branch-circuit short-circuit protection perform different jobs; neither can be selected from the voltage-drop percentage alone.
Key Considerations
The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 15 amp circuit at 100 feet?▾
Can I use aluminum wire for a 15 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator