What Size Wire for 15 Amp 150 Feet Away
Table-based wire size estimate for 15 amps at 150 feet on a 120V single-phase circuit. Immediate answer below.
Updated November 12, 2026
Recommended Wire Size
Required ampacity: 15 A × 1 = 15 A. Drop uses 15 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 150 ft.
Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).
Wire Comparison Table
| Wire Size | Ampacity | V-Drop (V) | V-Drop (%) | V at Load | Status |
|---|---|---|---|---|---|
| 12 AWG | 20A | 7.811V | 6.51% | 112.19V | |
| 10 AWG | 30A | 4.739V | 3.95% | 115.26V | |
| 8 AWGREC | 40A | 3.138V | 2.61% | 116.86V | |
| 6 AWG | 55A | 2.026V | 1.69% | 117.97V | |
| 4 AWG | 70A | 1.328V | 1.11% | 118.67V |
Table shows nearby candidate sizes for 15A at 150 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.
Sensitive loads at the remote endpoint
For electronics or controls on a long branch, identify the device’s minimum input voltage and any startup or ride-through requirement. A percentage result is useful only against that equipment limit. If several devices are distributed along the route, the lumped-end model places them all at the far end and may be conservative.
Why this copper conductor?
8 AWG has a site ampacity of 40 A against a required 15 A. Table 9 lists R = 0.78 and XL = 0.065 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.6972 Ω/kft. Substituting the actual load into 2 × 15 × 150 × 0.6972 / 1000 gives 3.138 V (2.61%).
The next smaller size, 10 AWG, has 30 A of site ampacity and 3.95% drop on this route. It fails the voltage-drop target.
3% route-length limit: 172.1 ft one way; remaining margin: 22.1 ft. This margin excludes upstream loss and does not authorize extra load.
Which assumption changes this selection?
copper: 15 A · 150 ft · 120 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).
| Assumption | Load / route / supply | Required ampacity | Minimum size | Drop / end voltage |
|---|---|---|---|---|
| Present route, 3% target | 15 A / 150 ft / 120 V | 15 A | 8 AWG | 3.138 V (2.61%) / 116.862 V |
| Reserve more voltage: 2% target | 15 A / 150 ft / 120 V | 15 A | 6 AWG | 2.026 V (1.69%) / 117.974 V |
| General branch circuit: Same assumed watts at twice the supply voltage | 7.5 A / 150 ft / 240 V | 7.5 A | 14 AWG | 6.015 V (2.51%) / 233.985 V |
The higher-voltage row keeps assumed electrical power constant by halving current. It is useful only for equipment listed for that alternative supply; it does not authorize reconnecting a fixed-voltage appliance. The percent drop changes with both current and supply voltage.
3% → 2% changes 8 AWG → 6 AWG. Load-voltage gain: 1.112 V. Original conductor’s 2% length limit: 114.7 ft one way.
Key Considerations
The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.
For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.
Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.
Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.
Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.
Frequently Asked Questions
What size wire do I need for a 15 amp circuit at 150 feet?▾
Can I use aluminum wire for a 15 amp circuit?▾
What happens if the voltage drop exceeds 3%?▾
Related Wire Size Calculations
Need a Custom Calculation?
Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.
Wire Size Calculator