Wire Sizing

What Size Wire for 15 Amp 150 Feet Away

Table-based wire size estimate for 15 amps at 150 feet on a 120V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
8 AWG
Voltage drop: 2.61% (3.138V)
Voltage at load: 116.86V
Ampacity used: 40 A (60°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
6 AWG
Voltage drop: 2.71% (3.250V)
Voltage at load: 116.75V
Ampacity used: 40 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 15 A × 1 = 15 A. Drop uses 15 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 150 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
12 AWG20A7.811V6.51%112.19V
10 AWG30A4.739V3.95%115.26V
8 AWGREC40A3.138V2.61%116.86V
6 AWG55A2.026V1.69%117.97V
4 AWG70A1.328V1.11%118.67V

Table shows nearby candidate sizes for 15A at 150 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Sensitive loads at the remote endpoint

For electronics or controls on a long branch, identify the device’s minimum input voltage and any startup or ride-through requirement. A percentage result is useful only against that equipment limit. If several devices are distributed along the route, the lumped-end model places them all at the far end and may be conservative.

Why this copper conductor?

8 AWG has a site ampacity of 40 A against a required 15 A. Table 9 lists R = 0.78 and XL = 0.065 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.6972 Ω/kft. Substituting the actual load into 2 × 15 × 150 × 0.6972 / 1000 gives 3.138 V (2.61%).

The next smaller size, 10 AWG, has 30 A of site ampacity and 3.95% drop on this route. It fails the voltage-drop target.

3% route-length limit: 172.1 ft one way; remaining margin: 22.1 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 15 A · 150 ft · 120 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target15 A / 150 ft / 120 V15 A8 AWG3.138 V (2.61%) / 116.862 V
Reserve more voltage: 2% target15 A / 150 ft / 120 V15 A6 AWG2.026 V (1.69%) / 117.974 V
General branch circuit: Same assumed watts at twice the supply voltage7.5 A / 150 ft / 240 V7.5 A14 AWG6.015 V (2.51%) / 233.985 V

The higher-voltage row keeps assumed electrical power constant by halving current. It is useful only for equipment listed for that alternative supply; it does not authorize reconnecting a fixed-voltage appliance. The percent drop changes with both current and supply voltage.

3% → 2% changes 8 AWG → 6 AWG. Load-voltage gain: 1.112 V. Original conductor’s 2% length limit: 114.7 ft one way.

Key Considerations

The entered current is a load assumption, not a breaker selection. If the load is continuous, determine its required ampacity separately; the generic calculation uses a factor of 1.

For small copper and aluminum conductors, the recommendation retains the site’s NEC 240.4(D) overcurrent limits. A higher insulation temperature rating does not by itself allow a larger breaker.

Verify cable type and terminal temperature before using the 75°C column. For example, a cable or termination limited to 60°C can require a different conductor even when the voltage-drop calculation passes.

Check the appliance’s supply range and any upstream loss. The calculation assumes the stated voltage at the beginning of this run and does not model receptacle contacts or loose connections.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a 15 amp circuit at 150 feet?▾
For a 15A/120V circuit at 150 feet, use 8 AWG copper (2.61% drop) or 6 AWG aluminum. The ampacity check uses 15A; voltage drop uses the actual 15A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 15 amp circuit?▾
At 15A over 150 ft, use 6 AWG aluminum (2.71% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 116.4V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator