Wire Sizing

What Size Wire for 15 Amp 150 Feet Away

Pre-calculated NEC-compliant wire size for 15 amps at 150 feet on a 120V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
8 AWG
Voltage drop: 2.92% (3.5V)
Voltage at load: 116.5V
Controlling factor: Voltage Drop (3% limit)
Aluminum
4 AWG
Voltage drop: 1.91% (2.29V)
Voltage at load: 117.7V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 150 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A14.13V11.78%105.9V
12 AWG20A8.91V7.43%111.1V
10 AWG30A5.58V4.65%114.4V
8 AWGREC50A3.5V2.92%116.5V
6 AWG65A2.21V1.84%117.8V
4 AWG85A1.39V1.16%118.6V
3 AWG100A1.1V0.92%118.9V
2 AWG115A0.87V0.73%119.1V
1 AWG130A0.69V0.58%119.3V
1/0 AWG150A0.55V0.46%119.5V
2/0 AWG175A0.44V0.36%119.6V
3/0 AWG200A0.34V0.29%119.7V
4/0 AWG230A0.27V0.23%119.7V
250 kcmil255A0.23V0.19%119.8V
300 kcmil285A0.19V0.16%119.8V
350 kcmil310A0.17V0.14%119.8V
400 kcmil335A0.14V0.12%119.9V
500 kcmil380A0.12V0.1%119.9V

Table shows all standard AWG/kcmil sizes for 15A at 150 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 15A circuit at 150 feet on 120V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 15 amp service at 150 feet?
For a 15A/120V circuit at 150 feet, use 8 AWG copper (2.92% drop) or 4 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 15 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 15A at 150 feet, use 4 AWG aluminum (1.91% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 15A circuit at 150 feet on 120V, exceeding 3% means the load receives less than 116.4V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator