Wire Sizing

Wire Size for Well Pump — 15 Amp 100 Feet

Pre-calculated NEC-compliant wire size for 15 amps at 100 feet on a 120V single-phase circuit. Immediate answer below.

Recommended Wire Size

Copper
8 AWG
Voltage drop: 1.95% (2.33V)
Voltage at load: 117.7V
Controlling factor: Voltage Drop (3% limit)
Aluminum
6 AWG
Voltage drop: 2.02% (2.42V)
Voltage at load: 117.6V
Controlling factor: Voltage Drop (3% limit)

Based on NEC Table 310.16 (75°C column), single-phase, 120V, 3% max voltage drop, one-way distance 100 ft.

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
14 AWG15A9.42V7.85%110.6V
12 AWG20A5.94V4.95%114.1V
10 AWG30A3.72V3.1%116.3V
8 AWGREC50A2.33V1.95%117.7V
6 AWG65A1.47V1.23%118.5V
4 AWG85A0.92V0.77%119.1V
3 AWG100A0.74V0.61%119.3V
2 AWG115A0.58V0.48%119.4V
1 AWG130A0.46V0.39%119.5V
1/0 AWG150A0.37V0.3%119.6V
2/0 AWG175A0.29V0.24%119.7V
3/0 AWG200A0.23V0.19%119.8V
4/0 AWG230A0.18V0.15%119.8V
250 kcmil255A0.15V0.13%119.8V
300 kcmil285A0.13V0.11%119.9V
350 kcmil310A0.11V0.09%119.9V
400 kcmil335A0.1V0.08%119.9V
500 kcmil380A0.08V0.06%119.9V

Table shows all standard AWG/kcmil sizes for 15A at 100 ft on 120V (copper). Green check = meets both ampacity and 3% voltage drop. REC = smallest compliant size.

Key Considerations

For a 15A circuit at 100 feet on 120V, both ampacity and voltage drop must be satisfied. NEC recommends keeping the total voltage drop (feeder + branch) under 5%, with no more than 3% on either segment alone.

Copper conductors at 75°C column (THHN/THWN-2) are assumed. If using 60°C terminations, derate the ampacity to the 60°C column values. Verify the temperature rating of your terminals.

Frequently Asked Questions

What size wire do I need for a 15 amp service at 100 feet?
For a 15A/120V circuit at 100 feet, use 8 AWG copper (1.95% drop) or 6 AWG aluminum. This keeps voltage drop within the NEC-recommended 3% limit.
Can I use aluminum wire for a 15 amp circuit?
Yes. Aluminum wire is a cost-effective alternative for larger circuits. For 15A at 100 feet, use 6 AWG aluminum (2.02% voltage drop). Aluminum requires AL-rated connectors and anti-oxidant compound at all terminations.
What happens if the voltage drop exceeds 3%?
Voltage drop above 3% reduces equipment efficiency, can cause motors to overheat, and may violate NEC 210.19(A) Informational Note No. 4. For a 15A circuit at 100 feet on 120V, exceeding 3% means the load receives less than 116.4V, which can damage sensitive electronics and shorten appliance lifespan.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator