Wire Sizing

Wire Size for Well Pump — 30 Amp 500 Feet

Table-based wire size estimate for 30 amps at 500 feet on a 240V single-phase circuit. Immediate answer below.

Updated November 12, 2026

Recommended Wire Size

Copper
2 AWG
Voltage drop: 2.50% (6.001V)
Voltage at load: 234.00V
Ampacity used: 95 A (60°C column). Controlling factor: Voltage Drop (3% limit)
Aluminum
1/0 AWG
Voltage drop: 2.49% (5.969V)
Voltage at load: 234.03V
Ampacity used: 100 A (60°C column). Controlling factor: Voltage Drop (3% limit)

Required ampacity: 30 A × 1 = 30 A. Drop uses 30 A. Ampacity: NEC Table 310.16, 60°C column (NEC 110.14(C) default for circuits of 100 A or less; equipment marked for 75°C terminals can allow the 75°C column), single-phase, 240V, 3% max voltage drop, one-way distance 500 ft.

Voltage drop uses AC resistance and reactance from NEC Chapter 9 Table 9 (NEC 2017 Table 9 values) for conductors in steel conduit at 0.85 lagging power factor, effective Z = R × PF + XL × sin(acos PF), single-phase, one set, VD = 2 × I × Z × L / 1000. Ampacity uses NEC 2023 Table 310.16 at 30°C ambient with no more than three current-carrying conductors. These are the same engine and defaults as the wire size calculator (steel conduit, PF 0.85).

Wire Comparison Table

Wire SizeAmpacityV-Drop (V)V-Drop (%)V at LoadStatus
4 AWG70A8.853V3.69%231.15V
3 AWG85A7.307V3.04%232.69V
2 AWGREC95A6.001V2.5%234V
1 AWG110A4.981V2.08%235.02V
1/0 AWG125A3.929V1.64%236.07V

Table shows nearby candidate sizes for 30A at 500 ft on 240V (copper). Green check = meets both ampacity and 3% voltage drop (Table 9, steel conduit, PF 0.85). REC = smallest size meeting these two model checks. See the full conductor tables for other sizes.

Long cable, splice and source review

At this route length, map every cable section and splice instead of assuming one uninterrupted surface conductor. The impedance calculation excludes splice contact loss and source regulation. Confirm the pump maker’s length limits, inspect the permitted underwater connection system, and consider the voltage available while another large load starts on the same source.

Why this copper conductor?

2 AWG has a site ampacity of 95 A against a required 30 A. Table 9 lists R = 0.2 and XL = 0.057 Ω/kft (steel conduit), so at PF 0.85 its effective Z is 0.2000 Ω/kft. Substituting the actual load into 2 × 30 × 500 × 0.2000 / 1000 gives 6.001 V (2.50%).

The next smaller size, 3 AWG, has 85 A of site ampacity and 3.04% drop on this route. It fails the voltage-drop target.

3% route-length limit: 599.9 ft one way; remaining margin: 99.9 ft. This margin excludes upstream loss and does not authorize extra load.

Which assumption changes this selection?

copper: 30 A · 500 ft · 240 V. Alternatives are hypothetical; all results use the same Table 9 model (Table 9, steel conduit, PF 0.85).

AssumptionLoad / route / supplyRequired ampacityMinimum sizeDrop / end voltage
Present route, 3% target30 A / 500 ft / 240 V30 A2 AWG6.001 V (2.50%) / 233.999 V
Reserve more voltage: 2% target30 A / 500 ft / 240 V30 A1/0 AWG3.929 V (1.64%) / 236.071 V
Well pump: Hypothetical down-well cable adds 25% to route30 A / 625 ft / 240 V30 A1 AWG6.226 V (2.59%) / 233.774 V

The additional route represents cable omitted below the wellhead. It changes impedance loss without changing running current. Replace the assumed extra length with the measured depth and actual route; starting behavior still needs its own check.

3% → 2% changes 2 AWG → 1/0 AWG. Load-voltage gain: 2.072 V. Original conductor’s 2% length limit: 399.9 ft one way.

Key Considerations

Include the cable down the well as well as the horizontal trench and the route from the panel to the wellhead. The entered distance is the complete one-way electrical path, not just the surface separation.

The stated amperes are assumed running current. The estimate applies no motor allowance: separately determine code full-load current and the applicable conductor factor under Article 430. A continuous-duty single motor commonly requires 125% of code full-load current, which need not equal measured running current.

A submersible motor must start against its hydraulic load. Check the pump maker’s cable-length limits and starting-voltage requirements; a steady-state calculation cannot model a pressure switch, control box or generator transient.

Verify submersible cable, underwater splice and terminal suitability. Pump overload protection and branch-circuit short-circuit protection perform different jobs; neither can be selected from the voltage-drop percentage alone.

Reference: NFPA 70 (NEC), including Articles 215, 240, 310, 430, 440, 547, 625 and 680 as applicable. Verify the adopted edition and equipment instructions. These are calculated examples, not installation approvals.

Frequently Asked Questions

What size wire do I need for a well-pump running-load estimate at 500 feet?▾
For a 30A/240V circuit at 500 feet, use 2 AWG copper (2.50% drop) or 1/0 AWG aluminum. The ampacity check uses 30A; voltage drop uses the actual 30A (NEC Chapter 9 Table 9 impedance, Table 9, steel conduit, PF 0.85). Installation adjustments and equipment ratings must be checked separately.
Can I use aluminum wire for a 30 amp circuit?▾
At 30A over 500 ft, use 1/0 AWG aluminum (2.49% voltage drop). Use only equipment and connectors listed for this aluminum gauge; follow their preparation instructions.
What happens if the voltage drop exceeds 3%?▾
3% is a planning target, not installation approval. Here it means 232.8V at the load before upstream loss. Compare the combined path with the equipment’s operating range.

Need a Custom Calculation?

Different voltage, three-phase, or custom max drop percentage? Use our interactive calculator.

Wire Size Calculator